Alsecure XGB Cca 2x10
Alsecure XGB Cca 2x10
ALSECURE XGB Cca is an installation cable for low voltage installations of 0.6/1kV with halogen-free outer sheath. ALSECURE XGB Cca is used in domestic and industrial fixed installations. ALSECURE XGB Cca can be used both indoors and outdoors. ALSECURE XGB Cca can also be placed underground in a well-draining tube. The cable is suitable for use at ambient temperatures between -20°C and + 80°C.
ALSECURE XGB Cca has fire reaction class Cca-s1,d2,a1 according to EN 50575 and may be installed in bundle or side by side according to AREI/RGIE. The cable is also suited for areas where AREI/RGIE imposes s1 a1.
- Nexans ref. : 10537743
- EAN : 5413404309979
Description
Description
Standards
-
ProductNBN HD 604 Part 5/Sect.L
Design
- Copper core, solid (Class 1) or stranded (Class 2) depending on cross-section
- Cross-linked polyethylene (XLPE) insulation (X)
- Filling compound or tape halogen-free
- Outer sheath in halogen-free thermoplastic material (G) - Colour: GREEN
Installation
- In cable conduit
- In cable duct
- Embedded in concrete, cement or walls
- In open air
- In industries
- In houses
- Underground installation is allowed provided the cable is installed in a sufficiently drained tube
Note
- Operating temperatures down to -20°C are permitted, provided that no mechanical forces are applied and the cable is not moved.
- UV-resistance according to EN 50289-4-17 Method A (duration test: 720h) establishing ALSECURE XGB is particularly fitted for our Belgian climate.
More on UV resistance
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Conductor flexibility
Solid class 1
Conductor shape
Circular solid (RE)
Insulation
XLPE (chemical)
Core identification
Blue, brown
With Green/Yellow core
No
Material of filler / inner sheath
Compound or tape
Outer sheath
Halogen free polyolefin
Sheath colour
Green
Halogen free
Yes
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Number of cores
2
Conductor cross-section
10 mm²
Neutral conductor section (when smaller)
- mm²
Cross-section of the protection cores
- mm²
Nominal outer diameter
12.9 mm
Approximate weight
347 kg/km
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
0,6/1 kV
Test voltage
4 kV
Permissible current rating in open air
75 A
Perm. current rating in air 30°C - flat formation
- A
Perm. current rating in air 30°C - trefoil formation
- A
Voltage drop, single phase
4.0 V/A.km
Mechanical characteristics
Mechanical characteristics
Impact resistance Max (IEC 30364-5-51)
6 J
Usage characteristics
Usage characteristics
Bending factor when laying
12 (xD)
Field of application
Indoor, Outdoor
U.V resistance
EN 50289-4-17 method A, for 720h
Max. conductor temperature in service
90 °C
Operating temperature, range
-20 ... 80 °C
Minimum installation temperature
0 °C
Resistance to vibrations
Moderate
Water proof
Temporary
Length
- m
Metric marking
Continuous
Packaging
Cut to length
Resources
Resources
Declaration of Performance
- Declaration of Performance n� : 1000223-BEBU
- Certification Date : 12/1/23
- AVCP (Assessment and Verification of Constancy of Performance) : System 1+
- Notified body : NB 2658
- Declared performance : Cca-s1,d2,a1