XVB Cca 9G1,5 mm²
XVB Cca 9G1,5 mm²
Nexans XVB Cca is an installation cable for low voltage installations of 0.6/1kV with PVC outer sheath. XVB Cca is used in domestic and industrial fixed installations. XVB Cca can be used both indoors and outdoors, provided it is shielded from direct sunlight. XVB Cca may also be placed underground in a well-draining tube. The cable is suitable for use at ambient temperatures ranging from -20°C to +80°C. Nexans XVB Cca has a fire reaction class of Cca-s3,d2,a3 according to EN 50575 and can be installed in bundles or side by side.
Read more- Nexans ref. : 10537901
- EAN : 5413404306473
Description
Description
Standards
-
ProductNBN HD 604 Part 4/Sect.G
Design
- Copper core, solid (Class 1) or stranded (Class 2)
- Cross-linked polyethylene (XLPE) insulation (X)
- Filling compound or tape
- Fire-retardant PVC oversheath (V) - colour: Grey
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Conductor flexibility
Solid class 1
Conductor shape
Circular solid (RE)
Insulation
XLPE (chemical)
Core identification
Green/Yellow, black numbers
With Green/Yellow core
Yes
Material of filler / inner sheath
Compound or tape
Outer sheath
PVC
Sheath colour
Grey
Halogen free
No
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Number of cores
9
Conductor cross-section
1.5 mm²
Ground conductor cross-section
- mm²
Neutral conductor section (when smaller)
- mm²
Average insulation thickness
0.7 mm
Insulation thickness of smaller conductor
- mm
Minimum outer sheath thickness
1.09 mm
Nominal outer diameter
16.9 mm
Approximate weight
291 kg/km
Electrical characteristics
Electrical characteristics
Test voltage
4 kV
Perm. current rating in air 30°C - flat formation
- A
Permissible current rating in open air
15 A
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Impact resistance Max (IEC 30364-5-51)
6 J
Usage characteristics
Usage characteristics
Bending factor when laying
12 (xD)
Field of application
Indoor, Outdoor
Max. conductor temperature in service
90 °C
Operating temperature, range
-20 ... 80 °C
Minimum installation temperature
0 °C
Resistance to vibrations
Moderate
Water proof
Good
Length
- m
Packaging
Cut to length
Metric marking
Continuous
Resources
Resources
Selling & delivery Information
Maximum permissible current for single cores are given for installation in trefoil.
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania