Nexans ALSECURE® PLUS 5G16
Nexans ALSECURE® PLUS 5G16
Halogen-free 300/500V rigid cables, fire-resistant CR1 C1 SECURE EFECTIS, with copper core, silicone insulation and orange sheath. All ALSECURE PLUS cables are manufactured in France.
Read more- Nexans ref. : 10045389
- EAN : 3427650006799
Description
Description
Standards
-
ProductIEC 60228; NBN-IEC 502-NAD
-
TestNBN 713-020; NBN C30-004 cat. F2
Application
Nexans ALSECURE® PLUS and Nexans ALSECURE® PREMIUM cables are designed to be used in safety systems (emergency lights, warning systems, fire fighting equipments, etc ...) in all premises open to the public (concert hall, theaters, cinemas, department stores, hospitals, schools, etc ...), in high-rises buildings, in tunnels, in industries.
Nexans ALSECURE® PLUS and Nexans ALSECURE® PREMIUM cables are fire resistant and fire retardant, low smoke and halogen free. In the event of fire, emitted gazes are non corrosive and have a very low toxicity.
Installation
Nexans ALSECURE® PLUS and Nexans ALSECURE® PREMIUM cables will be installed in accordance with the current regulation.
Nexans ALSECURE® PLUS and Nexans ALSECURE® PREMIUM cables have to be protected against direct sun lighting when it used outside
In case of laying between 0°C and -10°C, warm up the cables in a heated room 48 hours minimum before installation.
Fire performance
- Fire resistant according to NF C 32-070 Cat. CR1, resistance fire test EFECTIS SECURISE
- Fire retardant according to IEC/EN 60332-3-24, IEC/EN 60332-1-2, NF C 32-070 Cat. C1 & C2
- Low smoke : IEC/EN 61034, NF C 32-073
- Halogen free : IEC/EN 60754-1, NF C 32-074
- Low corrosivity : IEC/EN 60754-2, NF C 32-074
COMPLEMENTS
Core identification
(in accordance with european harmonization HD 308 S2)
1 x : white
2 x : brown - blue
3 x : brown - black - grey
3G : brown - blue - green/yellow
4 x : brown - black - grey - blue
4G : brown - black - grey - green/yellow
5 x : black cores with printed numbers
5 G : blue - brown - black - grey - green/yellow
7 cores and above : white cores with printed numbers
Type Approval
LCIE: Laboratoire Central des Industries Electriques
Current rating Capacities
The data are indicated for continuous duty operation and apply to:
- Maximum conductor temperature = 90 °C
- Nominal frequencies = 50 or 60 Hz
- One cable in free air (on perforated trays)
- Ambient temperature = 30 °C
Data recording from IEC 60364-5-52 or NF C 15-100
Voltage Drop
The data are based on Cos ø = 0.8
Minimum bending Radius
r = 6 x cable outer diameter
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Documentation
Selling & delivery Information
Marking
Solid class 1 cables :
ALSECURE PREMIUM "nx(or G )S" mm2 NF-USE 336 300/500V NF C 32-310 CR1/C1 SECURISE EFECTIS FRANCE
Stranded class 2 cables :
ALSECURE PLUS "nx(or G)S" mm2 NF-USE 279 300/500V NF C 32-310 CR1/C1 SECURISE EFECTIS FRANCE week / year
n: number of cores S: conductor cross-section (mm²)
G: with Green/Yellow x: without Green/Yellow